S/E 001LP Single Ended Roof Anchor
SE001LP
Roof anchor point
All exposed Safetor Anchors meet the requirements of the AS/NZS
1891.2:2001 Standards Horizontal Lifeline and Rail Systems and AS/NZS
1891.4:2009 Standards Industrial Fall Arrest Systems and Devices
Product Technical Statement
Design
The S/E 001LP anchor is designed to be bolted to a structural member.
This anchor can be used for Fall-Arrest, Abseiling and as an end anchor for lifelines.
Manufactured from 30mm Mild Steel bar with an overall height of 200mm.
This anchor is best suited for roofing with a low profile.
The Mounting plate is Manufactured from 10mm Mild Steel with two x 18mm
holes on either side of the main shaft.
Load reduction
The Safetor S/E001 anchor can reduce the loading on the structure to 3.8kN
Certification
The S/E 001LP Anchor has been fully tested to the AS/NZS 1891.4:2009 Standards by Material & Testing Laboratories.
Applications as per AS/NZS 1891.4:200 Standards: Strength Requirements for anchorages.
Ultimate Strength
End anchor for horizontal lifeline - 44kN
1 Person - Free Fall Arrest - 15kN
2 Person - Free Fall Arrest - 21kN
1 person - Limited Free Fall Arrest - 12kN
NB
1. Anchorage strength applicable when using restraint
technique, is either 15kN or 12kN depending on whether
the ultimate fall is Free-Fall
or Limited Free-Fall.
2.'Ultimate Strength' means that the anchorage may yield
at the stated load but must not fail.
Anchor Material:
Mild Steel 30mm Black Bar 300 grade
Mild Steel 10mm Black Bar 300 grade
Mild Steel 10mm Light Plate 250 grade
Bolting
Bolts used on this anchor are 4 x M16mm construction bolts.
Blasting
Profile blasted to remove all scale and grease
etc.
Coatings
Kulorthene ABCITE® THERMOPLASTIC POWDER COATINGS
Kulorthene
Series ABCITE® thermoplastic powder coatings have been developed
specifically for enhanced long term corrosion protection, high impact
strength and excellent exterior weathering. Read more...
Installation
The installation should only be carried out by a competent person as set out in the AS/NZS 1891.4:2009 Standards.
CCL provides a warranty on product performance of the anchor and not the structure.
It is the responsibility of the Installer, Building Designer or Building Owner to ensure that the structure to which the
anchor is attached to will support a load of at least 15kN as set out in the AS/NZS 1891.4:2009 Standards.
If there is any doubt about the structures adequacy a Structural Engineer should be consulted.